HVAC Occupancy Sensor
In stock
$0.00
This incentive is available for the addition of occupancy sensors to HVAC systems, enabling automatic adjustment of temperature setpoints and airflow rates based on occupancy.
You have a saved application!
You can either continue where you left off or start over. Starting a new application will delete your saved progress.
Required Documentation:
• Floor Plans and Controlled Area: Detailed plans highlighting the areas where occupancy sensors will be installed and the zones they will control.
• HVAC documentation (e.g., BAS graphic screenshot, control programming, sequence of operations, functional testing documentation).
• Proposed control documentation should illustrate how occupancy sensors will modify airflow setpoints and temperature setpoints to achieve energy savings.
• Applicability: Eligible for both retrofit projects and new construction with spaces that are heated with natural gas.
• Qualifying Efficiency Requirement:
o Occupancy sensors must be capable of reducing the minimum airflow to the zone from ≥30% to ≤15% of the design flow rate.
o Must allow for a setback/setup of space temperature setpoints by a minimum of 5°F in both heating and cooling modes when the space is unoccupied.
• Exclusions:
o Spaces are already controlled by outside air demand control ventilation (DCV) systems.
o Cannot be combined with incentives for setback/setup control or energy management systems.
• Other requirements: The room must be equipped with mechanical cooling and natural gas heating systems.